ACI Logo aci@acicontrols.com

MY ACCOUNT
MY SHOPPING CART
LOG IN

  Enter Stock Code, Model No., or Keywords
TRANSFORMERS - CONTROL
Previous Page | Next Page | View Printer-Friendly Page

  • UL Listed
  • 10 - 32 Terminal Screws
  • Accepts large inrush currents to power control circuits, small motors and small solenoid valves
  • Secondary Fuse Holder included as Standard - Fuse NOT FURNISHED
  • Optional Primary Fuse Holder available - see below - Fuses NOT FURNISHED


120 / 230 PRIMARY to 24 SECONDARY VAC

VA

OUTPUT AMPS

A

B

C

D

E

MOUNTING SLOTS

CATALOG NUMBER

WT
(lbs)

 

50

2.08

3

3

2 9/16

2

2 1/2

13/64 X 3/8

106837M

2.6

100

4.17

3 3/8

3 3/8

2 7/8

2 3/8

2 13/16

13/64 X 3/8

106831M

4.4

SUGGESTED SECONDARY FUSE
(NOT INCLUDED)

FUSE TYPE

FUSE
AMPS

CATALOG NUMBER

WT
(lbs)

 

FLM

3 2/10

118780

0.1

FLM

6 1/4

118785

0.1

230 / 460 PRIMARY to 24 SECONDARY VAC

VA

OUTPUT AMPS

A

B

C

D

E

MOUNTING SLOTS

CATALOG NUMBER

WT
(lbs)

 

50

2.08

3

3

2 9/16

2

2 1/2

13/64 X 3/8

106832M

2.7

100

4.17

3 3/8

3 3/8

2 7/8

2 3/8

2 13/16

13/64 X 3/8

106834M

4.2

 

SUGGESTED SECONDARY FUSE
(NOT INCLUDED)

FUSE TYPE

FUSE
AMPS

CATALOG NUMBER

WT
(lbs)

 

FLM

3 2/10

118780

0.1

FLM

6 1/4

118785

0.1

208 / 277 PRIMARY to 120 SECONDARY VAC

VA

OUTPUT AMPS

A

B

C

D

E

MOUNTING SLOTS

CATALOG NUMBER

WT
(lbs)

 

50

0.42

3

3

2 9/16

2

2 1/2

13/64 X 3/8

116141M

2.9

100

0.83

3 3/8

3 3/8

2 7/8

2 3/8

2 13/16

13/64 X 3/8

116351M

4.5

 

SUGGESTED SECONDARY FUSE
(NOT INCLUDED)

FUSE TYPE

FUSE
AMPS

CATALOG NUMBER

WT
(lbs)

 

FLM

6/10

107220

0.1

FLM

1 1/4

107221

0.1

230 / 460 PRIMARY to 120 SECONDARY VAC

VA

OUTPUT AMPS

A

B

C

D

E

MOUNTING SLOTS

CATALOG NUMBER

WT
(lbs)

 

50

0.43

3

3

2 9/16

2

2 1/2

13/64 X 3/8

106838M

2.6

100

0.87

3 3/8

3 3/8

2 7/8

2 3/8

2 13/16

13/64 X 3/8

106836M

4.2

150

1.30

4

3 3/4

3 3/16

2 7/8

3 1/8

13/64 X 3/8

106983M

6.7

200

1.74

4 1/4

4 1/2

3 13/16

2 1/2

3 3/4

13/64 X 3/8

106936M

8.5

250

2.17

4 3/4

4 1/2

3 13/16

2 7/8

3 3/4

13/64 X 3/8

106881M

10.0

 

SUGGESTED SECONDARY FUSE
(NOT INCLUDED)

FUSE TYPE

FUSE
AMPS

CATALOG NUMBER

WT
(lbs)

 

FLM

6/10

107220

0.1

FLM

1 1/4

107221

0.1

FLM

2

107014

0.1

FLM

2 1/2

118778

0.1

FLM

3 2/10

118780

0.1

208 / 230 / 460 PRIMARY to 120 SECONDARY VAC

VA

OUTPUT AMPS

A

B

C

D

E

MOUNTING SLOTS

CATALOG NUMBER

WT
(lbs)

 

50

0.43

3 1/8

3

2 9/16

2 1/8

2 1/2

13/64 X 3/8

107012M

2.8

100

0.87

3 11/16

3 3/8

2 7/8

2 11/16

2 13/16

13/64 X 3/8

106833M

4.9

150

1.30

4 3/16

3 3/4

3 3/16

3 1/16

3 1/8

13/64 X 3/8

107016M

7.4

200

1.74

4 1/4

4 1/2

3 13/16

2 3/4

3 3/4

13/64 X 3/8

107017M

9.4

250

2.17

4 3/4

4 1/2

3 13/16

3 1/4

3 3/4

13/64 X 3/8

106599M

11.1

 

SUGGESTED SECONDARY FUSE
(NOT INCLUDED)

FUSE TYPE

FUSE
AMPS

CATALOG NUMBER

WT
(lbs)

 

FLM

6/10

107220

0.1

FLM

1 1/4

107221

0.1

FLM

2

107014

0.1

FLM

2 1/2

118778

0.1

FLM

3 2/10

118780

0.1

 

Previous Page | Next Page

 