ACI Logo aci@acicontrols.com

MY ACCOUNT
MY SHOPPING CART
LOG IN

  Enter Stock Code, Model No., or Keywords
PUMP PANELS
Previous Page | Next Page | View Printer-Friendly Page

  • UL 508 Disconnect Switch with lockable handle assembly
  • Lockable handle assembly can be padlocked in the "OFF" position with up to three (3) padlocks (not furnished)
  • Motor fuseblock for each motor
  • IEC motor starter for each motor
  • Adjustable motor overload with Reset button for each motor
  • Control transformer standard on panels 230 Volt and above: Fused primary on panels above 50 Amps (fuse included) Fused secondary (fuse included)
  • H-O-A selector switch for each motor
  • Pilot light for each motor
  • "LEAD 1 - LEAD 2" selector switch
  • Terminal strip for connecting floats, pressure switches, etc.
  • Ground screw or lug
  • Type 4 metal enclosure
  • Alternation optional - see below
   
NOTE: MOTOR FUSES ARE NOT INCLUDED - SEE FUSE SECTION FOR PROPER FUSES

120 Volt Single Phase
Motor
HP
ContACTOR
TYPE.
OVERLOAD Amp Range Disconnect
Size
(Amps)

Max Wire Size(awg)

Fuse Holder Type 4x Enclosure
Size Type Enclosure
Size (INCHES)
WT
Lbs
CATALOG
NUMBER
1/3 S11 5.5 - 7.5 40 10 J 30 24 x 16 x 8 47 137704
1/3 S11 7.2 - 10 40 10 J 30 24 x 16 x 8 47 137704
1/2 S11 9.0 - 12.5 40 10 J 30 24 x 16 x 8 47 137705
3/4 S11 11.3 - 16 40 10 J 30 24 x 16 x 8 47 137706
1 S11 11.3 - 16 40 10 J 30 24 x 16 x 8 47 137706
3/4 S11 15 - 20 40 10 J 30 24 x 16 x 8 47 137706A
1 S11 15 - 20 40 10 J 30 24 x 16 x 8 47 137706A
1 1/2 S11 17 - 21.5 40 10 J 30 24 x 16 x 8 47 137707
1 1/2 S11 21 - 25 40 10 J 30 24 x 16 x 8 47 137707A
2 S11 24.5 - 30 60 10 J 60 24 x 16 x 8 47 137708
3 S18 24 - 36 60 8 J 60 24 x 16 x 8 49 137709
5 S22 45 - 60 100 8 J 100 30 x 20 x 8 76 137710


230 Volt Single Phase
MOTOR
HP
CONTACTOR
TYPE
OVERLOAD
Amp RANGE
DISCONNECT
SIZE
(Amps)
MAX WIRE
SIZE
(AWG)
FUSE HOLDER
TYPE 4 ENCLOSURE
TYPE
SIZE
(Amps)
ENCLOSURE
SIZE (Inches)
WT
Lbs
CATALOG
NUMBER
1/2 S11 4.0 - 6.0 40 10 J 30 24 x 16 x 8 50 137711
3/4 S11 5.5 - 7.5 40 10 J 30 24 x 16 x 8 50 137712
1 S11 5.5 - 7.5 40 10 J 30 24 x 16 x 8 50 137712
3/4 S11 7.2 - 10 40 10 J 30 24 x 16 x 8 50 137712A
1 S11 7.2 - 10 40 10 J 30 24 x 16 x 8 50 137712A
1 1/2 S11 9.0 - 12.5 40 10 J 30 24 x 16 x 8 50 137713
2 S11 9.0 - 12.5 40 10 J 30 24 x 16 x 8 50 137713
3 S11 11.3 - 16 40 10 J 30 24 x 16 x 8 50 137714
3 S11 15 - 20 40 10 J 30 24 x 16 x 8 50 137714A
5 S18 24.5 - 30 60 8 J 60 24 x 16 x 8 52 137715
7 1/2 S18 35 - 47 100 8 J 100 30 x 20 x 8 79 137716
10 S25 45 - 60 100 6 J 100 30 x 20 x 8 81 137717

Options (consult factory):
  1. Alternation with “LEAD 1 - LEAD 2 - AUTO” selector switch.
  2. Phase Monitor - electronic for Three (3) Phase Panels.
  3. Pilot Light - full voltage with incandescent lamp and standard legend.
  4. LED Lamps to replace incandescent lamp in Pilot Light, consult factory.
  5. For other versions or options, Consult Factory
 
 

Previous Page | Next Page

 

ACI Advance Controls Inc.