ACI Logo aci@acicontrols.com

MY ACCOUNT
MY SHOPPING CART
LOG IN

  Enter Stock Code, Model No., or Keywords
CONTACTORS, STARTERS, INDUSTRIAL CONTROL RELAYS > Technical Data
Previous Page | Next Page | View Printer-Friendly Page
C Series Contactors - Technical Data

 
CONTACTOR
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
RM06
C06
RN09
C09
C12
C16
C23
C28
C32
C40
UL RATINGS
 
 
 
 
 
 
 
 
 
 
Rated Voltage
600
600
600
600
600
600
600
600
600
600
General Purpose Amps
16
16
24
24
24
32
35
40
50
60
Maximum HP (60 Hz)
 
 
 
 
 
 
 
 
 
 
1 PH 120 Volt
-
1/2
-
3/4
1
1 1/2
2
2
3
3
230 Volt
-
1 1/2
-
2
2
3
3
5
5
7 1/2
3 PH 200 Volt
-
2
-
3
5
5
7 1/2
7 1/2
10
15
230 Volt
-
3
-
3
5
5
7 1/2
10
10
15
460 Volt
-
5
-
5
7 1/2
10
15
20
25
30
575 Volt
-
5
-
7 1/2
10
10
15
20
30
40
IEC RATINGS
 
 
 
 
 
 
 
 
 
 
AC1 Resistive Amps
16
16
25
24
24
32
35
40
50
60
AC3 Inductive Amps
-
9
-
9
12
16
23
28
32
40
AC3 KW (50 Hz)
 
 
 
 
 
 
 
 
 
 
3 PH 220 Volt
-
2.2
-
.8
6.8
6.8
9.6
9.6
13.7
16.5
380 Volt
-
4
-
12
12
12
16.5
16.5
23.7
28.5
415 Volt
-
4
-
12.5
12.5
12.5
18
18
25.5
31
660 Volt
-
4
-
13.5
13.5
13.5
19
19
27.5
33
COIL DATA (60 Hz)
 
 
 
 
 
 
 
 
 
 
AC Inrush VA
26
26
70
70
70
70
82
82
215
215
AC Sealed VA
4.2
4.2
12
12
12
12
15
15
27
27
Voltage Limits (% Nominal)
 
 
 
 
 
 
 
 
 
 
Maximum
+10
+10
+10
+10
+10
+10
+10
+10
+10
+10
Minimum
-30
-30
-30
-30
-30
-30
-30
-30
-30
-30
PHYSICAL DATA
 
 
 
 
 
 
 
 
 
 
Electrical Life (x 106)
2
0.9
2
2.2
2
1.8
2
2
2
1.8
Mechanical Life x 106)
5
5
10
10
10
10
10
10
10
10
Max. Switching Frequency
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
Contactor Mounting (deg)
+/- 30
+/- 30
+/- 30
+/- 30
+/- 30
+/- 30
+/- 30
+/- 30
+/- 30
+/- 30
Operational Temperature °F
-4/+150
-4/+150
-4/+150
-4/+150
-4/+150
-4/+150
-4/+150
-4/+150
-4/+150
-4/+150
AUXILIARY CONTACTS
 
 
 
 
 
 
 
 
 
 
Std. / Max.
4/8
1/5
4/12
1/9
1/9
1/9
2/10
2/10
2/10
2/10
Rated Voltage
600
600
600
600
600
600
600
600
600
600
Rated Current
10
10
10
10
10
10
10
10
10
10
TERMINALS
 
 
 
 
 
 
 
 
 
 
Cable Size (Maximum)
 
 
 
 
 
 
 
 
 
 
mm2
2.5
2.5
4
4
4
4
10
10
16
16
AWG
10
10
10
10
10
10
8
8
6
6
Power Terminal Torque (lb-ft)
0.75
0.75
1.3
1.3
1.3
1.3
1.7
1.7
2.9
2.9

 
CONTACTOR
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
C50
C65
C80
C95
C105
C130
UL RATINGS
 
 
 
 
 
 
Rated Voltage
600
600
600
600
600
600
General Purpose Amps
72
85
104
125
130
150
Maximum HP (60 Hz)
 
 
 
 
 
 
1 PH 120 Volt
5
5
7 1/2
10
10
-
230 Volt
10
15
15
15
15
-
3 PH 200 Volt
15
20
25
30
30
40
230 Volt
20
25
30
30
40
50
460 Volt
40
50
60
60
75
100
575 Volt
50
60
60
75
100
100
IEC RATINGS
 
 
 
 
 
 
AC1 Resistive Amps
72
85
104
125
130
150
AC3 Inductive Amps
50
65
80
95
105
130
AC3 KW (50 Hz)
 
 
 
 
 
 
3 PH 220 Volt
19.2
22
27.5
30
30
37
380 Volt
33.2
38
47.5
55
55
60
415 Volt
36
41.5
51.8
55
55
63
660 Volt
38.5
44
55
65
65
75
COIL DATA (60 Hz)
 
 
 
 
 
 
AC Inrush VA
280
280
280
300
300
300
AC Sealed VA
32
32
32
63
63
63
Voltage Limits (% Nominal)
 
 
 
 
 
 
Maximum
+10
+10
+10
+10
+10
+10
Minimum
-25
-25
-25
-20
-20
-20
PHYSICAL DATA
 
 
 
 
 
 
Electrical Life (x 106)
1.8
1.8
1.8
2
1.7
1.5
Mechanical Life x 106)
10
10
10
10
10
10
Max. Switching Frequency
600
600
600
600
600
600
Contactor Mounting (deg)
+/- 25
+/- 25
+/- 25
+/- 25
+/- 25
+/- 25
Operational Temperature °F
-4/+150
-4/+150
-4/+150
-4/+150
-4/+150
-4/+150
AUXILIARY CONTACTS
 
 
 
 
 
 
Std. / Max.
4/12
4/12
4/12
4/8
4/8
4/8
Rated Voltage
600
600
600
600
600
600
Rated Current
10
10
10
10
10
10
TERMINALS
 
 
 
M8
BOLT
M8
BOLT
M8
BOLT
Cable Size (Maximum)
 
 
 
mm2
35
35
35
AWG
1
1
1
Power Terminal Torque (lb-ft)
3.7
3.7
3.7

CONTACTOR
C160
C200
C250
C320
UL RATINGS
 
 
 
 
Rated Voltage
600
600
600
600
General Purpose Amps
200
240
260
350
Maximum HP (60 Hz)
 
 
 
 
1 PH 120 Volt
-
-
-
-
230 Volt
-
-
-
-
3 PH 200 Volt
50
60
75
100
230 Volt
60
75
100
125
460 Volt
125
150
200
250
575 Volt
125
150
200
250
IEC RATINGS
 
 
 
 
AC1 Resistive Amps
200
240
260
350
AC3 Inductive Amps
160
200
250
320
AC3 KW (50 Hz)
 
 
 
 
3 PH 220 Volt
45
55
65
90
380 Volt
80
95
120
160
415 Volt
80
100
125
160
660 Volt
100
110
132
200
COIL DATA (60 Hz)
 
 
 
 
AC Inrush VA
700
700
300
300
AC Sealed VA
88
88
63
63
Voltage Limits (% Nominal)
 
 
 
 
Maximum
+10
+10
+10
+10
Minimum
-20
-20
-20
-20
PHYSICAL DATA
 
 
 
 
Electrical Life (x 106)
1.4
1.2
1.1
1
Mechanical Life x 106)
10
10
10
10
Max. Switching Frequency
600
600
600
600
Contactor Mounting (deg)
+/- 25
+/- 25
+/- 25
+/- 25
Operational Temperature °F
-4/+150
-4/+150
-4/+150
-4/+150
AUXILIARY CONTACTS
 
 
 
 
Std. / Max.
4/8
4/8
4/8
4/8
Rated Voltage
600
600
600
600
Rated Current
10
10
10
10
TERMINALS
 
 
 
 
Cable Size (Maximum)
 
 
 
 
mm2
M8
M10
M10
M10
AWG
BOLT
BOLT
BOLT
BOLT
Power Terminal Torque (lb-ft)
 
 
 
 

Utilization Categories (A.S. 1029)
AC1 Non Inductive or slightly inductive loads: Power Factor not less than 0.95. Example: Distribution and electric resistance heating.
AC2 Slip ring motors: Starting and switching OFF running loads. Effective values: Making 2.5 x le; Breaking 1 x le; Power Factor = 0.65
AC3 Squirrel cage motors: Starting and switching OFF running loads. Effective values: Making 6 x le; Breaking 1 x le; Power Factor = 0.65
AC4 Squirrel cage motors: Starting, inching, plugging, reversing. Effective values: Making 6 x le; Breaking 6 x le; Power Factor = 0.65
UL File Number:   Contactors - E155477
Overloads - E221485
All data presented herein was considered accurate at the time of publication.
All data is subject to change without notice and without incurring any obligation by ACI.
ADVANCE CONTROLS, INC. is not responsible for typographical or clerical errors.
 

Previous Page | Next Page

 

ACI Advance Controls Inc.
© 2017 Advance Controls, Inc. | 800.559.9ACI | 941.746.3221 | 4505 18th Street East, Bradenton FL 34203